The protection and management of MV/LV transformers in a rural environment requires specific circuit breakers compatible with significant load differences, thus ensuring full exploitation of the installed power, even in unbalanced operation.
Technical characteristics
1- Post circuit breaker with digital trip unit
|
Reference strandard |
HN 63-S-11 |
HN 63-S-11 |
|
Voltage rating |
440Ⅴ |
440V |
|
Current rating |
165A |
265 A |
|
Cutout power |
4000A |
6400A |
|
Closing power |
6800A |
11700A |
|
Number of poles |
4 |
4 |
|
Numberofoutputs |
1 ouput |
2 outputs |
|
Cable sections |
25/70mm2 |
50/150mm2 |
|
Breakdownvoltage .pulse/earth .at 50 Hz .between poles |
20KV 10KV 4KV |
20KV 10KV 4KV |
|
Controlsystem |
Manual |
Manual |
|
Installation |
on post |
on post |
The micro-controller assesses the transformer temperature in real time, based on the currents in the three phases and the external ambient temperature. This ambient temperature is computed based on the probe and a mathematical model that is also a function of the three phase currents.